AirGap 400/10
For ordering:
Send an e-mail to info@radonett.se
Please specify the product you are interested in and your contact information, including: Delivery and invoice information
Product specification
AirGap 400/10 backflow preventer category 5 type AB is type approved according to EN 1717. Installation is quick and easy. It can be placed on the floor and uses a minimal amount of space.
AirGap backflow preventer is based on our radon aerator design, which is currently used in 7 countries and has been tested for more than 150 million operating hours!
- Operating pressure: 400 l/min at 10 bar
- Maximum pressure: 14 bar
- Maximum outlet flow: 489 l/min
- Weight (empty): 185 kg
- Height: 1 750 mm
- Width: 1 100 mm
- Depth: 700 mm
- Volume: 510 liters
- Tank material: Acid-resistant Aisi 316
- Water inlet: Ball valve, R40, (1 ½”) internal with Bürkert 5282 NC R40 solenoid valve, (1 ½”) soft-closing
- Water outlet: Ball valve, R50, (2”) internal.
- Balancing valve: yes
- Frequency control: Vacon
- Alarm: System monitoring, overflow and pump alarm, dry running and operation indicator
- Dry running protection: yes
- Pump: Lowara 11 kW
- Pressure transmitter: Danfoss 0-16 bar
- Voltage: 3x 400 V or 3x230V
- Rated current: 20.2A (400 V) or 35A (230V)
- Installation: On the floor in premises with floor drain and non-freezing environment.
Contact Radonett for more information and for installation manual